special filter for 690V inverter
1.Reducing the conducted emission from inverter to power network.
2.Improve the reliability of the whole system.
3.less than 100A filters, using solid safety connector, more than 200A filters, using copper bar
4.Low leakage current,Lack of a phase, The maximum leakage current is 13. 12mA (except P type).
Technical Data
1.Rated voltage: 690/380 VAC
2.Rated frequency: 50Hz
3.Rated current: 120A~ 1000A
3.High potential test voltage : P-E 2850VDC/60sec P-P 2850VDC/60sec
4.Temperature range: -25C -100C (25/100/21 )
5.Design correspondingto : IEC/EN 60939
6.Typical work frequency : 150kHz- 30MHz
Filter Selection Table
Adapter inverter parameter
|
Filter type
|
Rated current
|
Connector code
|
Drive power rating
|
Rated vodtage
|
Input fter
|
Output fter
|
|
|
18.5kW
|
660- 690VAC
|
SKIBC25N10
|
SKO6C25N10
|
25A
|
N10
|
37kW
|
660-690VAC
|
SKI6C50N35
|
SKO6C50N35
|
50A
|
N35
|
55kW
|
660- 690VAC
|
SKI6C80N35
|
SKO6C80N35
|
80A
|
N35
|
75kW
|
660-690VAC
|
SKI6C100N35
|
SKO6C100N35
|
100A
|
N35
|
132kW
|
660-690VAC
|
SKI6C200N99
|
SKO6C200N99
|
200A
|
|
150kW
|
660-690VAC
|
SKI6C200N99
|
SKO6C200N99
|
|
|
185kW
|
660- 690VAC
|
SKI6C250N99
|
SKO6C250N99
|
250A
|
|
200kW
|
660-690VAC
|
SKI6C250N99
|
SKO6C250N99
|
|
|
250kW
|
660-690VAC
|
SKI6C350N99
|
SKO6C350N99
|
350A
|
|
315kW
|
660- 690VAC
|
SKIBC400N99
|
SKO6C400N99
|
400A
|
|
400kW
|
660-690VAC
|
SKI6C550N99
|
SKO6C550N99
|
550A
|
|
500kW
|
660-690VAC
|
SKI6C650N99
|
SKO6C650N99
|
650A
|
|
630kW
|
660-690VAC
|
SKIBC800N99
|
SKO6C800N99
|
800A
|
|
715kW
|
660-690VAC
|
SKI6C900N99
|
SKO6C900N99
|
900A
|
|
800kW
|
660-690VAC
|
SKI6C1000N99
|
SKO6C1000N99
|
1000A
|
|
Welcome to our website. If you have any requests or suggestions,please feel free to email us at info@safeinvert.com or